Idatha enemininingwane
I-ABB 07KT93 GJR5251300R0101 I-Advant Controller module
I-serial interface COM1 ivumela ukufinyelela kumayunithi ayisisekelo e-AC31/CS31 (07 KR 31, 07 KR 91, 07 KT 92 kuya ku-07 KT 94) kanye nephrosesa yezokuxhumana engu-07 KP 62 ye-ABB Procontic T200.
Wonke umsebenzi osebenzayo nowokuhlola we-PLC ungabizwa nge-ASCII plain text telegrams. Imodi yokusebenza "Imodi esebenzayo" kufanele isethwe kusixhumi esibonakalayo se-serial.
Amayunithi axhumeka:
 - Itheminali kwimodi ye-VT100
 - Ikhompyutha ene-emulation ye-VT100
 - Ikhompyutha enohlelo lokuphatha ama-telegrams ombhalo ocacile wemisebenzi yokusebenza nokuhlola
Imodi yokusebenza yesixhumi esibonakalayo:
 I-serial interface COM 1 kufanele isethelwe kumodi yokusebenza "Imodi esebenzayo" ukuze kusetshenziswe imisebenzi esebenzayo neyokuhlola.
RUN/MISA shintsha endaweni: MISA Endaweni yokushintsha YEKA, i-PLC ivamise ukumisa imodi yokusebenza "Imodi esebenzayo" ku-COM 1.
SHINTSHA/YIMA shintsha endaweni: RUN Esimeni sokushintsha GIJIMA, imodi yokusebenza "Imodi esebenzayo" isethwe ku-COM 1 lapho kuhlangatshezwana nemibandela eyodwa kwezimbili ezilandelayo:
 - Isistimu engashintshi KW 00,06 = 1
 or
 – Isistimu engaguquki i-KW 00,06 = 0 kanye ne-Pin 6 ku-COM1 inesignali engu-1 (isiginali engu-1 ku-Pin 6 isethwa kusetshenziswa ikhebula lesistimu 07 SK 90 noma ngokungaxhumi i-Pin 6)
Ukuziphatha kwesistimu ye-PLC
 Okulandelayo kuyasebenza:
 Ukucutshungulwa kohlelo lwe-PLC kubaluleke kakhulu kunokuxhumana ngezixhumi ezibonakalayo ze-serial.
I-PLC ilawula indlela eyamukelayo ye-serial interface COM1 ngokusebenzisa iziphazamiso. Ngesikhathi somjikelezo wohlelo lwe-PLC olusebenzayo, izinhlamvu ezingenayo ngokulandelana zicupha ukushaya kwenhliziyo, ziphazamise uhlelo lwe-PLC olusebenzayo kuze kube yilapho izinhlamvu ezitholiwe zigcinwa kusigcinalwazi sokwamukela. Ukuze ugweme ukuphazamiseka unomphela kokucutshungulwa kohlelo, i-PLC ilawula ukwamukelwa kwedatha ngomugqa we-RTS ukuze kwenzeke esikhaleni esiphakathi kwemijikelezo emibili ye-PLC.
I-PLC icubungula imisebenzi etholwe nge-COM1 kuphela ezikhaleni phakathi kwemijikelezo yohlelo lwe-PLC. Izinhlamvu nazo zikhishwa nge-COM1 kuphela ezikhaleni phakathi kwemijikelezo yohlelo emibili. Ukwehla kokusetshenziswa kwe-PLC kanye nokukhula kwezikhala phakathi kwemijikelezo yohlelo, kuyanda izinga lokuxhumana elingaba khona nge-COM1.
 
 		     			ABB 07KT93 GJR5251300R0101 I-Advant Controller module
Yiziphi ukusetshenziswa kwesilawuli semojuli ye-ABB 07KT93 GJR5251300R0101?
 Imojula yesilawuli se-ABB 07KT93 Advant iyingxenye yochungechunge lwe-Advant Controller 400 (AC 400), okuwuhlelo lokulawula kwesikhathi sangempela kanye nohlelo oluzenzakalelayo lwezinqubo zezimboni. Ivame ukusetshenziswa ekuqapheni izinhlelo zokusebenza ekukhiqizeni nasekusebenzeni kukagesi
Kungani imojula ye-07KT93 yehluleka ukuqala?
 Inkinga yokuxhumeka kwamandla: Hlola ukuthi ugesi we-24V DC uxhumeke ngokujwayelekile yini nokuthi intambo kagesi yonakele noma ayikhululekile yini. Imojuli ngokwayo ingase ibe nephutha. Zama ukushintsha imojuli entsha ukuze uyihlole.
 
 				

 
 							 
              
              
             